| AL1002ULADAJ (Replaces
Model AL1002UL2ADAJ)![]()
Model
AL1002ULADAJ is an extremely cost effective 10 amp voltage regulated remote
power supply/battery charger. It may be connected to any 24 volt Fire Alarm
Control Panel (FACP). Primary applications include Notification Appliance
Circuit (NAC such as strobes and horns) expansion support to meet ADA
requirements. It also provides auxiliary power to support system accessories.
The unit delivers regulated and filtered 24 volt power to Class B or Class A NAC
loop circuits. Additionally, a separate 1.0A auxiliary output with reset for
four (4)-wire smoke detectors is available. The 10 amp rated supply current can
be divided between the four (4) outputs for powering NAC devices. Each output is
rated at 2.5 amp max., and can be independently programmed for Steady, Temporal
Code 3 or Strobe Synchronization. All outputs may be programmed for Input to
Output Follower Mode (output will follow input. i.e. March Time Input, March
Time Output). An individual output of 4 amp is achieved by paralleling 2
outputs. In non-alarm condition independent loop supervision for Class A and/or
Class B FACP NAC circuits is provided. In the event of a loop trouble the FACP
will be notified via the steered input (input 1 or input 2). In addition, there
are common trouble output terminals (NC, C, NO) which are used to indicate
general loop/system trouble. A common trouble input is provided for optional NC
(normally closed) devices to report trouble to the FACP. Two (2) FACP signaling
outputs can be employed and directed to control supervision and power delivery
to any combination of the four (4
|