AL1012ULM![]()
Model AL1012ULM is specifically
designed for use with access control systems and accessories. This unit converts
a 115VAC 60Hz input into five (5) PTC protected Class 2 Rated power limited
outputs rated @ 2 amp each, with an output current of 12VDC @ 10 amp total.
|
|   |
• UL Listed for Access Control
Systems (UL294), CUL Listed - CSA Standard C22.2 No.205-M1983, Signal Equipment. File#
S4707.
Power
Supply/Charger: • 12VDC output. • 10 amp of continuous supply
current. • 115VAC 60Hz, 1.9 amp input. • Filtered and electronically
regulated outputs. • Short circuit and thermal overload protection. •
Built-in charger for sealed lead acid or gel type battery backup. • Maximum
charge current .7 amp. • Zero voltage drop upon transfer to battery
backup. • AC input and DC output LED indicators. • AC fail supervision
(form "C" contact rated @ 1 amp 28VDC). • Low battery and battery presence
supervision (form "C" contact rated @ 1 amp 28VDC). • Lifetime
Warranty.
Multi-Output Module: • Five (5) PTC protected
outputs. • Class 2 Rated power limited outputs. • Current limit is 2 amp @
12VDC per output. • Provides power for Fail Safe and/or Fail Secure locking
devices. • Fire Alarm Panel or Access Control System trigger inputs. NO or NC
supervised trigger input and polarity reversal trigger input (.4 amp draw from FACP). •
Lifetime
Warranty.
•
Accommodates up to two (2) 12VDC/12AH batteries. • Dimensions: 15.5"H x
12.23"W x 4.5"D. • 1.125" and 1.375" combination knockouts.
|
|