Specifications: 4WTA-B
Detection: Photoelectric
--------------------------------------------------------------------------------
Wiring: 4-wire
--------------------------------------------------------------------------------
Heat Sensor: 135°F (57.2°C) fixed
--------------------------------------------------------------------------------
Sounder: 85 dBA
--------------------------------------------------------------------------------
Operating Voltage: 12/24 V non-polarized nominal, 10 min. to 35 max.
--------------------------------------------------------------------------------
Maximum Ripple Voltage: 30% of nominal (peak to peak)
--------------------------------------------------------------------------------
Alarm Current: 35mA max.
--------------------------------------------------------------------------------
Standby Current: 50µA maximum average
--------------------------------------------------------------------------------
Alarm Contact Ratings: 0.5A @ 30V AC/DC
--------------------------------------------------------------------------------
Temperature Range: 32° to 100°F (0° to 37.8°C)
-------------------------------------------------------------------------------
Humidity Range: 0% to 95% RH, noncondensing
--------------------------------------------------------------------------------
Freeze Trouble: 41°F (5°C)
--------------------------------------------------------------------------------
Sensitivity: 2.5%/ft. nominal
-------------------------------------------------------------------------------
Wiring Gauge: 14-22 AWG
--------------------------------------------------------------------------------
Dimensions: 2.0" (51mm) H x 5.3" (127mm) Dia.
--------------------------------------------------------------------------------
Weight: 7.1 oz. (200 g)
|